Paragraph 1: The Incident and Initial Impact: On Tuesday, February 7, 2023, at approximately 6:30 am, a fire incident occurred at the Egbin Power Plc, significantly impacting the Transmission Company of Nigeria’s (TCN) operations. The fire, originating from one of Egbin Power’s service transformers, damaged TCN’s 150 Mega Volt Ampere (MVA) transformer located at the Egbin Transmission Substation. This substation plays a crucial role in supplying power to various areas within Lagos State and parts of Ibadan Electricity Distribution Company’s franchise area. The immediate consequence of the fire was a reduction in bulk power supply, affecting a total load of 47 megawatts (MW). This disruption primarily impacted the Ikorodu and Odogunyan 132/33kV transmission substations, which are key supply points for Ikeja Electricity Distribution Company (IKEDC) and portions of Ibadan Electricity Distribution Company’s coverage area. The incident also affected power transmission through Sagamu Line 1, Sagamu Line 2, and Maryland Line 2 on the 132kV network within Lagos State.

Paragraph 2: The Root Cause and Damage Assessment: Preliminary investigations conducted by TCN identified the root cause of the fire as a faulty 33kV instrument transformer (CT/VT) installed by Egbin Power. This faulty equipment ignited, ultimately leading to the damage of TCN’s 150MVA power transformer. The damage was substantial, causing a tear in the transformer’s main tank and subsequent oil leakage. This incident highlights the interconnectedness of the power grid and how equipment failures in one part of the system can have cascading effects on other crucial components. The damaged transformer is a vital link in the power transmission chain, and its failure placed additional strain on the remaining infrastructure.

Paragraph 3: Mitigation Efforts and Load Management: To mitigate the immediate impact of the transformer failure, TCN swiftly diverted the affected 47 MW load to a second 150MVA power transformer within the Egbin substation. However, this transfer placed the second transformer under significant strain, operating closer to its maximum capacity. Consequently, a capacity deficit emerged, necessitating load-shedding across all affected areas. Load-shedding is a controlled and temporary interruption of power supply to certain areas to manage the overall demand and prevent a complete system collapse. TCN promptly notified the affected distribution companies, IKEDC and Eko Electricity Distribution Company (EKEDC), urging them to implement load management strategies within their respective franchise areas to minimize the impact on consumers.

Paragraph 4: TCN’s Response and Restoration Plan: Recognizing the urgency of the situation, TCN initiated efforts to replace the damaged transformer and restore normal power supply. This involves sourcing a new 150MVA transformer, a complex undertaking that requires significant logistical coordination and potentially substantial lead times. While TCN has not provided a specific timeline for complete restoration, they have assured the public that they are working diligently to expedite the process. The statement released by TCN’s General Manager, Public Affairs, Mrs. Ndidi Mbah, emphasizes the company’s commitment to resolving the issue and minimizing the disruption to electricity consumers.

Paragraph 5: Communication and Apology: TCN has maintained open communication with the affected distribution companies and the public regarding the incident and the ongoing restoration efforts. Mrs. Mbah’s statement conveyed an apology for the inconvenience caused by the power disruption, acknowledging the impact on both the distribution companies and the end-users. This proactive communication is essential for managing public expectations and maintaining transparency during the restoration process. It also underscores TCN’s commitment to accountability and its recognition of the importance of reliable power supply for businesses and residents.

Paragraph 6: Long-Term Implications and Grid Resilience: This incident brings to light the vulnerability of the power grid to equipment failures and the importance of investing in robust infrastructure and preventative maintenance. The fire and subsequent transformer damage highlight the need for regular inspections and upgrades of critical equipment to minimize the risk of such incidents. Furthermore, it emphasizes the importance of redundancy within the grid, ensuring that backup systems are in place to handle unexpected outages. The incident also underscores the interconnected nature of the power system and the potential for localized failures to have widespread impacts. Going forward, a comprehensive review of grid infrastructure and maintenance practices is necessary to enhance grid resilience and minimize the risk of future disruptions. Investing in advanced monitoring and diagnostic tools could also help identify potential issues before they escalate into major failures.